Parameters; Inverter; Power Limitation - SMA SUNNY CENTRAL 500CP XT User Manual

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

SMA Solar Technology AG
11.2

Parameters

11.2.1 Inverter

11.2.1.1 Power Limitation

Name
Description
Plimit*
Limitation of the nominal
device power including
apparent power
Pmax**
Limitation of the nominal
power
P-WMod**
Mode for active power
limitation
User Manual
Value/range
Explanation
0 kW to 550 kW
Sunny Central 500CP XT
0 kW to 700 kW
Sunny Central 630CP XT
0 kW to 792 kW
Sunny Central 720CP XT
0 kW to 836 kW
Sunny Central 760CP XT
0 kW to 880 kW
Sunny Central 800CP XT
0 kW to 935 kW
Sunny Central 850CP XT
0 kW to 990 kW
Sunny Central 900CP XT
0 kW to 1100 kW
Sunny Central 1000CP XT
0 kW to 550 kW
Sunny Central 500CP XT
0 kW to 700 kW
Sunny Central 630CP XT
0 kW to 792 kW
Sunny Central 720CP XT
0 kW to 836 kW
Sunny Central 760CP XT
0 kW to 880 kW
Sunny Central 800CP XT
0 kW to 935 kW
Sunny Central 850CP XT
0 kW to 990 kW
Sunny Central 900CP XT
0 kW to 1100 kW
Sunny Central 1000CP XT
Off
Limits active power to Pmax
WCtlCom
Limits active power via an exter-
nal control unit, such as the
Power Reducer Box
WCnst
Manually limits active power in
kW (P-W) via communication de-
vices, such as the SC-COM
WCnstNom
Manually limits active power in %
(P-WNom) via communication
devices, such as the SC-COM
WCnstNomAnIn
Limits active power in % at the
analog input
WCnstNomDigIn
Limits active power at the digital
input. This mode is not supported.
11 Operating Data and Parameters
Default
value
550 kW
700 kW
792 kW
836 kW
880 kW
935 kW
990 kW
1,100 kW
550 kW
700 kW
792 kW
836 kW
880 kW
935 kW
990 kW
1,100 kW
Off
SCCPXT-E7-BA-en-58
121