SMA SUNNY CENTRAL 500CP XT User Manual page 99

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

10 Function Description
SMA Solar Technology AG
By supplying reactive power, the inverter performs voltage-stabilizing measures in the event of overvoltage or
undervoltage. The parameterization is carried out by means of a reactive power/voltage characteristic curve. The
characteristic curve can be flexibly configured by parameterizing the slope, a type of deadband through two voltage
points and a hysteresis.
Figure 28: Characteristic curve for reducing reactive power without deadband and without hysteresis
Figure 29: Characteristic curve for reducing reactive power with deadband and without hysteresis
User Manual
SCCPXT-E7-BA-en-58
99