SMA Solar Technology AG
Name
Description
Tm
Entry of current time
TolGr1*
Deviation of group 1 currents
from mean value
MoniTm-
Start time for monitoring of
Gr1On*
group 1
MoniTm-
End time for monitoring of
Gr1Off*
group 1
MoniTmGrAl-
Start time for monitoring of all
lOn*
groups
MoniTm-
End time for monitoring of all
GrAllOff*
groups
MoniTm-
Start time for monitoring of all
ComOn*
groups
MoniTmCo-
End time for monitoring of all
mOff*
groups
Ackn
Acknowledge errors
ErrLevGr1*
Sensitivity of error detection for
group 1
Parameter exists for all six groups
ComBaud*
Baud rate
User Manual
Value/range
Explanation
0 to 235959
Entered in the format HH-
MMSS
5% to 100%
Parameter exists for all six
groups.
07:00 a.m. to
Parameter exists for all six
7:00 p.m.
groups.
07:00 a.m. to
Parameter exists for all six
7:00 p.m.
groups.
07:00 a.m. to
7:00 p.m.
07:00 a.m. to
7:00 p.m.
07:00 a.m. to
7:00 p.m.
07:00 a.m. to
7:00 p.m.
quit
24 Sensitive
50 min ‒ 10%
24 Regular
50 min ‒ 14%
24 Insensitive
50 min ‒ 18%
32 Sensitive
35 min ‒ 10%
32 Regular
35 min ‒ 13%
32 Insensitive
35 min ‒ 16%
64 Sensitive
15 min ‒ 7%
64 Regular
15 min ‒ 9%
64 Insensitive
15 min ‒ 10%
1,200 baud
Parameter can only be
changed in the operating state
4,800 baud
"Stop".
9,600 baud
19,200 baud
38,400 baud
57,600 baud
11 Operating Data and Parameters
Default
value
13%
10:00 a.m.
3:00 p.m.
10:00 a.m.
3:00 p.m.
10:00 a.m.
3:00 p.m.
32 Regular
19,200
baud
SCCPXT-E7-BA-en-58