6 Operation
6.3.5.4

Displaying the Memory Capacity Available on the Memory Card

1. Log into the user interface (see Section 9.4.1, page 78).
2. Select Sunny Central > Info.
3. In the field Sunny Portal Buffer Load, you can see the space available in the internal ring buffer.
4. In the field SD card memory capacity, you can see the space available on the memory card.
6.4

Updating the Firmware

6.4.1

Automatic Update

If the communication unit has access to Sunny Portal, you can select automatic update of the firmware. The
communication unit checks whether a new firmware version is available every time data is transmitted to Sunny Portal.
If a new firmware update is available, the communication unit will download the firmware update from the Internet and
install it at night between 1:00 a.m. and 4:00 a.m (time set on the inverter). The automatic firmware update function is
disabled by default.
Requirement:
☐ Connection to Sunny Portal must be established (see Section 6.2.2, page 54).
Procedure:
1. Log into the user interface (see Section 9.4.1, page 78).
2. Select Sunny Central > Settings > Data transmission.
3. In the field Automatic firmware update, select the option yes.
4. Select the button [Save].
6.4.2

Update via User Interface

1. Log into the user interface (see Section 9.4.1, page 78).
2. Select Sunny Central > Info.
3. Select the button [Refresh] in the field VersionFirmware.
6.5

Changing the Insulation Monitoring

6.5.1

Insulation Monitoring with GFDI and Insulation Monitoring Device

6.5.1.1

Safety with insulation monitoring with GFDI and insulation monitoring device

Danger to life from electric shock due to live voltage
High voltages are present in the conductive components of the inverter. Touching live components results in death or
serious injury due to electric shock.
• After switching off the inverter, wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Wear suitable personal protective equipment for all work on the product.
• All work must be carried out in accordance with this document. All safety information must be observed.
• Do not touch any live components of the inverter or the medium-voltage grid. Comply with all applicable safety
regulations for handling medium-voltage grids.
Ground-fault monitoring with GFDI does not provide protection from personal injury.
60
SCCPXT-E7-BA-en-58
DANGER
SMA Solar Technology AG
User Manual