Name
Description
QoDQ-VAr-
Reactive power setpoint
Mod**
in the operating mode
"Q at Night"
Q-VAr
Reactive power in kVAr
User Manual
Value/range
Explanation
Off
Sets reactive power to 0 kVAr
and displacement power factor
cos φ to 1
VArCtlCom
Specifies reactive power via ex-
ternal control unit, such as the
Power Reducer Box
VArCnst
Specifies reactive power in kVAr
via the parameter QoDQ-VAr
VArCnstNom
Specifies reactive power in % via
the parameter QoDQ-VArNom
VArCnstNomAnIn
The reactive power setpoint is im-
ported via an analog input.
VArCtlVol
Specifies reactive power as a
function of the grid voltage
VArCtlVolHystDb
Specifies reactive power as a
function of the grid voltage (Q =
f(V) characteristic curve)
−245 kVAr to
Sunny Central 500CP XT
+245 kVAr
−310 kVAr to
Sunny Central 630CP XT
+310 kVAr
−346 kVAr to
Sunny Central 720CP XT
+346 kVAr
−365 kVAr to
Sunny Central 760CP XT
+365 kVAr
−385 kVAr to
Sunny Central 800CP XT
+385 kVAr
−409 kVAr to
Sunny Central 850CP XT
+409 kVAr
−433 kVAr to
Sunny Central 900CP XT
+433 kVAr
−485 kVAr to
Sunny Central 1000CP XT
+485 kVAr
11 Operating Data and Parameters
Default
value
Off
0 kVAr