12  Parameters

12.1.2 Grid Monitoring/Grid Limits

Name
HzCtlOpMin*
HzCtlOpMax*
HzCtlOpMaxRecon* Maximum connection frequency
HzCtlMax*
HzCtlMaxTm*
HzCtlhhLim*
HzCtlhhLimTm*
HzCtlhLim*
HzCtlhLimTm*
HzCtllLim*
HzCtllLimTm*
HzCtlllLim*
HzCtlllLimTm*
HzCtlMin*
HzCtlMinTm*
VCtlCharEna*
VCtlCharTm*
VCtlMax*
VCtlMaxTm*
98
SCCP-JP-BA-A4-en-12
Description
Minimum connection frequency
Maximum connection frequency
after grid error
Threshold for overfrequency
level 3
Tripping time for overfrequency
level 3
Threshold for overfrequency
level 2
Tripping time for overfrequency
level 2
Threshold for overfrequency
level 1
Tripping time for overfrequency
level 1
Threshold for underfrequency
level 1
Tripping time for underfrequency
level 1
Threshold for underfrequency
level 2
Tripping time for underfrequency
level 2
Threshold for underfrequency
level 3
Tripping time for underfrequency
level 3
Activation of dynamic
undervoltage detection
Start time of dynamic
undervoltage detection
Threshold for overvoltage release
level 3
Tripping time for overvoltage
level 3
Range
Explanation
45 Hz to 50 Hz
For 50 Hz grid
55 Hz to 60 Hz
For 60 Hz grid
50 Hz to 55 Hz
For 50 Hz grid
60 Hz to 65 Hz
For 60 Hz grid
50 Hz to 55 Hz
For 50 Hz grid
60 Hz to 65 Hz
For 60 Hz grid
50 Hz to 55 Hz
For 50 Hz grid
60 Hz to 66 Hz
For 60 Hz grid
0 ms to
1,000,000 ms
50 Hz to 55 Hz
For 50 Hz grid
60 Hz to 66 Hz
For 60 Hz grid
0 ms to
1,000,000 ms
50 Hz to 55 Hz
For 50 Hz grid
60 Hz to 66 Hz
For 60 Hz grid
0 ms to
1,000,000 ms
45 Hz to 50 Hz
For 50 Hz grid
55 Hz to 60 Hz
For 60 Hz grid
0 ms to
1,000,000 ms
45 Hz to 50 Hz
For 50 Hz grid
55 Hz to 60 Hz
For 60 Hz grid
0 ms to
1,000,000 ms
45 Hz to 50 Hz
For 50 Hz grid
55 Hz to 60 Hz
For 60 Hz grid
0 ms to
1,000,000 ms
Off
On
0 ms to
1,000,000 ms
100% to 150%
0 ms to
1,000,000 ms
SMA Solar Technology AG
Default value
49.5 Hz
59.4 Hz
50.5 Hz
60.6 Hz
50.5 Hz
60.6 Hz
0
0
52 Hz
62 Hz
600 ms
51 Hz
61.2 Hz
1,000 ms
49 Hz
58.8 Hz
1,000 ms
48 Hz
58 Hz
600 ms
47 Hz
57 Hz
600 ms
On
77 ms
0
0