Troubleshooting (OP: Central Remote Controller)
"MC"
3.4

Address Duplication, Improper Setting

MC
Remote
Controller
Display
Applicable
Central remote controller
Models
Method of
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Detection
Malfunction
Two units are both set to master controller mode or slave controller mode.
Decision
Conditions
Supposed
Causes
Troubleshooting
234
Address duplication of centralized remote controller
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Are
two or more central
remote controllers
connected?
NO
YES
SiUS30-604
Disconnect all central remote
controllers except one and
reset the power supply of the
central remote controller.
Reset power supply of the
central remote controller.
(V2835)