Specifications; Rxlq-Ta, Rxlq-Tb - Daikin VRV Aurora RXLQ-TATJU Series Service Manual

Table of Contents

Advertisement

Specifications

5. Specifications
5.1

RXLQ-TA, RXLQ-TB

Model name
Power supply
1 Cooling capacity
Nominal
Rated
2 Heating capacity
Nominal
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Compressor
Type
Displacement
Number of revolutions
Motor output ×
Number of units
Starting method
Fan
Type
Motor output
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Gas pipe
Weight
3 Sound pressure level (Reference data)
3 Sound power level (Reference data)
Safety devices
Defrost method
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Standard accessories
Drawing No.
Notes:
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5
1.
m) for 72/96 class or 75 ft. (23 m) for 120 class for non-ducted indoor units, level difference: 0 ft. (0 m).
Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5 m)
2.
for 72/96 class or 75 ft. (23 m) for 120 class for non-ducted indoor units, level difference: 0 ft. (0 m).
Anechoic chamber conversion value, measured under ISO standard conditions. During actual operation, these values may be higher as a result of ambient conditions.
3.
Sound pressure level may increase during heating operation at ambient temps below 41°F (5°C) value in parenthesis the max sound pressure at those conditions.
4.
19
RXLQ72TATJU(A)
3 phase, 208/230 V, 60 Hz
72,000 (21.1)
Btu/h
(kW)
69,000 (20.2)
81,000 (23.7)
Btu/h
(kW)
77,000 (22.6)
Ivory white (5Y7.5/1)
66-11/16 × 48-7/8 × 30-3/16
in (mm)
(1,694 × 1,242 × 767)
Cross fin coil
Hermetically sealed scroll type
m³/h
12.7
r/min
3,738
kW
3.9 × 1
Soft start
Propeller fan
kW
0.80 × 2
cfm
7,283 (206)
(m³/min)
Direct drive
 3/8 (9.5) C1220T
in (mm)
(Brazing connection)
 3/4 (19.1) C1220T
in (mm)
(Brazing connection)
lbs (kg)
727 (330)
dB (A)
60 (65 4)
dB
79
High pressure switch,
Fan driver overload protector,
Overcurrent fuse,
Inverter overload protector,
Leak detecting device
Deicer
%
10.7 ~ 100
R-410A
lbs (kg)
25.8 (11.7)
Electronic expansion valve
Installation manual,
Operation manual,
Connection pipes, Clamps
4D112564A
RXLQ96TATJU(A)
3 phase, 208/230 V, 60 Hz
96,000 (28.1)
92,000 (27.0)
108,000 (31.7)
103,000 (30.2)
Ivory white (5Y7.5/1)
66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767)
Cross fin coil
Hermetically sealed scroll type
17.5
3,294
5.0 × 1
Soft start
Propeller fan
0.80 × 2
7,989 (226)
Direct drive
 3/8 (9.5) C1220T
(Brazing connection)
 7/8 (22.2) C1220T
(Brazing connection)
793 (360)
61 (67 4)
80.5
High pressure switch,
Fan driver overload protector,
Overcurrent fuse,
Inverter overload protector,
Leak detecting device
Deicer
12.8 ~ 100
R-410A
25.8 (11.7)
Electronic expansion valve
Installation manual,
Operation manual,
Connection pipes, Clamps
4D112565A
SiUS341802EC
RXLQ120TATJU(A)
3 phase, 208/230 V, 60 Hz
120,000 (35.2)
114,000 (33.4)
135,000 (39.6)
129,000 (37.8)
Ivory white (5Y7.5/1)
66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767)
Cross fin coil
Hermetically sealed scroll type
23.1
4,350
6.6 × 1
Soft start
Propeller fan
0.80 × 2
8,806 (249)
Direct drive
 1/2 (12.7) C1220T
(Brazing connection)
 1-1/8 (28.6) C1220T
(Brazing connection)
793 (360)
63.5 (67 4)
84.5
High pressure switch,
Fan driver overload protector,
Overcurrent fuse,
Inverter overload protector,
Leak detecting device
Deicer
11.7 ~ 100
R-410A
25.8 (11.7)
Electronic expansion valve
Installation manual,
Operation manual,
Connection pipes, Clamps
4D112566A