Setting Notes - Siemens SIPROTEC 7SA522 Manual

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

2 Functions
2.1.2.3

Setting Notes

Fault Annuncia-
tions
2.1.2.4
Settings
Addr.
Parameter
610
FltDisp.LED/LCD
615
Spont. FltDisp.
640
Start image DD
2.1.2.5
Information List
No.
Information
-
Test mode
-
DataStop
-
SynchClock
-
>Light on
-
HWTestMod
-
Error FMS1
-
Error FMS2
-
Brk OPENED
-
FdrEARTHED
1
Not configured
38
Pickup of a new protective function generally turns off any previously lit LEDs, so that
only the latest fault is displayed at any time. It can be selected whether the stored LED
displays and the spontaneous annunciations on the display appear upon renewed
pickup, or only after a renewed trip signal is issued. In order to enter the desired type
of display, select the submenu General Device Settings in the SETTINGS menu. At
address  )OW'LVS/('/&' the two alternatives 7DUJHW RQ 38 and 7DUJHW
RQ 75,3 ("No trip - no flag") are offered.
For devices with graphical display use parameter  6SRQW )OW'LVS to specify
whether or not a spontaneous annunciation will appear automatically on the display
(<(6) or not (12). For devices with text display such messages will appear after a
system fault in any case.
After startup of a device featuring a 4-line display, measured values are displayed by
default. Use the arrow keys on the device front to select the different represenations
of the measured values for the so-called default display. The start page of the default
display, which is displayed by default after startup of the device, can be selected via
parameter  6WDUW LPDJH ''. The available representation types for the mea-
sured values are listed in the appendix .
Setting Options
Target on PU
Target on TRIP
NO
YES
image 1
image 2
image 3
image 4
image 5
Type of In-
formation
IntSP
IntSP
IntSP_Ev
SP
IntSP
OUT
OUT
IntSP
IntSP
SP
Default Setting
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of flt.annun-
ciations
image 1
Start image Default Display
Comments
Test mode
Stop data transmission
Clock Synchronization
>Back Light on
Hardware Test Mode
Error FMS FO 1
Error FMS FO 2
Breaker OPENED
Feeder EARTHED
No Function configured
Comments
7SA522 Manual
C53000-G1176-C155-3