Settings for Analog Output

The following describes the settings for outputting the current measurement results from the analog output of
the 20-pole terminal block.
Setting the analog output destination
With analog output, the measurement results can be output converted to a current from 4 to 20 mA or a voltage
from -10 to +10 V.
Selects which to output, the current or the voltage.
Important
The same output destination is set for all banks. The output destination cannot be set separately for individual banks.
Item
Setting item
Sensor settings
Analog output
1
Set the operating mode to the FUN mode.
3-3 Switching operation modes p.57
Explorer pane
 Edit pane
2
Select the output destination from [Analog
output].
Note
The analog output destination can also be set with key operations on the Sensor Controller.
Setting the analog output destination p.264
138
Parallel I/O connection
Setting value
Description
Voltage output
Voltage output
(default value)
Current output
Current output
: [Device Group] | [(Sensor Name)] | [System]
[System Data] (double-click)
: [Sensor settings] icon (
)
ZW User's Manual