Functions
Delays
Minimum Voltage
6.12.2.1 Settings for Frequency Protection
For 60 Hz systems:
Addr.
LCD-Text
5401
FCT 81 O/U
5402
Vmin
5404
81–1 PICKUP
5405
81–1 DELAY
5407
81–2 PICKUP
5408
81–2 DELAY
5410
81–3 PICKUP
5411
81–3 DELAY
5413
81–4 PICKUP
5414
81–4 DELAY
For 50 Hz systems:
Addr.
LCD-Text
5401
FCT 81 O/U
5402
Vmin
5403
81–1 PICKUP
5405
81–1 DELAY
5406
81–2 PICKUP
5408
81–2 DELAY
5409
81–3 PICKUP
5411
81–3 DELAY
5412
81–4 PICKUP
5414
81–4 DELAY
6-122
The time delays (Definite Time) entered at addresses , , and ,
allow the device to prioritize or order corrective actions based on the degree to which
the actual system frequency departs (upward or downward) from the nominal system
frequency.
The minimum voltage is set at address 9PLQ. If the positive sequence voltage
is less than this value, the frequency protection is blocked.
Setting Options
OFF
ON
~
40
120 V
~
55.50
64.50 Hz
~
0.00
100.00 sec.
~
55.50
64.50 Hz
~
0.00
100.00 sec.
~
55.50
64.50 Hz
~
0.00
100.00 sec.
~
55.50
64.50 Hz
~
0.00
100.00 sec.
Setting Options
OFF
ON
~
40
120 V
~
45.50
54.50 Hz
~
0.00
100.00 sec.
~
45.50
54.50 Hz
~
0.00
100.00 sec.
~
45.50
54.50 Hz
~
0.00
100.00 sec.
~
45.50
54.50 Hz
~
0.00
100.00 sec.
Default Setting
OFF
81 Over/Under
Frequency Protection
65 V
Minimum required
voltage for operation
59.50 Hz
81-1 Pickup
60.00 sec.
81-1 Time Delay
59.00 Hz
81-2 Pickup
30.00 sec.
81-2 Time Delay
57.50 Hz
81-3 Pickup
3.00 sec.
81-3 Time delay
61.00 Hz
81-4 Pickup
30.00 sec.
81-4 Time delay
Default Setting
OFF
81 Over/Under
Frequency Protection
65 V
Minimum required
voltage for operation
49.50 Hz
81-1 Pickup
60.00 sec.
81-1 Time Delay
49.00 Hz
81-2 Pickup
30.00 sec.
81-2 Time Delay
47.50 Hz
81-3 Pickup
3.00 sec.
81-3 Time delay
51.00 Hz
81-4 Pickup
30.00 sec.
81-4 Time delay
Comments
Comments
7SJ62 Manual
C53000-G1140-C121-1