10.11 Start Inhibit for Motors (66/68)

Setting Ranges /
Resolutions
Restarting Limit
10-30
Starting Current
Relative to Nominal Motor Current
Nominal Motor Current
Maximum Permissible
Starting Time
Temperature
Equalization Time
Maximum Permissible
Number of Warm Starts
Difference between
Cold and Warm Starts
Extension K-Factor for
Cooling Simulations of
Rotor at Rest
1
) For I
= 1 A, divide all limits by 5.
N
I
/I
3.0 to 10.0
Start
Motor nom
I
1.0 A to 6.0 A
Motor nom
T
3 s to 120 s
Start Max
T
0.0 min to 60.0 min
Equal
n
1 to 4
warm
n
- n
1 to 2
cold
warm
kτ-Factor
1 to 10
Θ
RESTART
Where:
Θ
Restart
Θ
Rot.max.perm
n
Cold
(Increments 0.1)
1
)
(Increments 0.5 A)
(Increments 1 s)
(Increments 0.1 min)
(Increments 1)
(Increments 1)
(Increments 1)
n
COLD
Θ
=
-------------------------- -
Rot.max.perm
n
COLD
Temperature limit below
which restarting is possible
maximum permissible motor
over-temperature (= 100 % in
operating measured value
Θ
)
Rot
Rot trip
Number of permissible
restarts from cold state
7SJ62 Manual
C53000-G1140-C121-1
1
)
1