Functions
Addr.
LCD-Text
7103
BLK MAN. CLOSE NO
7105
TIME RESTRAINT 0.50
7108
SAFETY 79 ready
7113
CHECK CB?
7115
CB TIME OUT
7116
MAX.InhibitTIME
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7140
ZONE SEQ.CO-
ORD.
7150
50–1/50N–1
7151
50–2/50N–2
7152
51/51N
7153
67–1/67N–1
7154
67–2/67N–2
6-138
Setting Options
Default Setting
NO
YES
~
320.00 sec. 3.00 sec.
~
0.01
300.00 sec. 15.00 sec.
No check
No check
Chk each cycle
~
0.10
320.00 sec. 3.00 sec.
~
0.01
320.00 sec. 15.00 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0.01
320.00 sec. 0.50 sec.
~
0
9
1
~
0
9
1
OFF
OFF
ON
No influence
No influence
Starts 79
Stops 79
No influence
No influence
Starts 79
Stops 79
No influence
No influence
Starts 79
Stops 79
No influence
No influence
Starts 79
Stops 79
No influence
No influence
Starts 79
Stops 79
Comments
Block automatic reclosing dur-
ing manual closing of breaker
(01 - BI)
Reset time of automatic reclos-
ing
Safety time until automatic re-
closing is ready
Check breaker position indica-
tion before attempting a reclos-
ing shot
Breaker ready monitoring time
Maximum inhibit time of auto re-
closing allowed for external bi-
nary input
Dead Time 1, Phase Fault
Dead Time 1, Ground Fault
Dead Time 2, Phase Fault
Dead Time 2, Ground Fault
Dead Time 3, Phase Fault
Dead Time 3, Ground Fault
Dead Time 4-9, Phase Fault
Dead Time 4-9, Ground Fault
Number of reclosing attempts
for ground faults
Number of reclosing attempts
for phase faults
Zone sequence coordination
50–1 and 50N–1 supervision of
automatic reclosing
50–2 and 50N–2 supervision of
automatic reclosing
51 and 51N supervision of auto-
matic reclosing
67–1 and 67N–1 supervision of
automatic reclosing
67–2 and 67N–2 supervision of
automatic reclosing
Ordering Code
7SJ62**–
X
X
X
X
X
X
X
X
X
X
X
-
X
X
-
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
7SJ62 Manual