Siemens SIPROTEC 7SJ62 Instruction Manual page 107

Multi-functional protective relay with bay controller
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Information
7SJ62 Manual
C53000-G1140-C121-1
mation group. This is particularly useful if the information group is associated with a
function that contains settings.
If the information group belongs to a protective function for the relay, a dialog window
can be accessed in which the settings of the protective function may be modified. The
procedure for entering settings of a protective function is described in general in Chap-
ter 4. Details regarding the settings for various functions are found in Chapter 6.
The settings group to be processed may be selected via the menu item 9LHZ → 6HW
WLQJ *URXS.
The column header ,QIRUPDWLRQ comprises the function number, the brief text (dis-
play text), an explanation (long text), and the information type. The following abbrevi-
ations are used for the information types:
• Messages:
− SP
Single Point Indication
− DP
Double Point Indication
− OUT
Output Indication
− IntSP
Internal Single Point Indication
− IntDP
Internal Double Point Indication
− TxTap
Transformer Tap Changer
− Ev
Event
• Commands:
− C_S
Single Command with Single Output without feedback
− CF_S
Single Command with Single Output with feedback
− C_SN
Single Command with Single Output Negated without
feedback
− CF_SN
Single Command with Single Output Negated with feedback
− C_D2
Double Command (2 relays) with Single Outputs without
feedback
− CF_D2
Double Command (2 relays) with Single Outputs with
feedback
− C_D12
Double Command with Single Trip Outputs and Double Close
Outputs without feedback
− CF_D12
Double Command with Single Trip Outputs and Double Close
Outputs with feedback
− C_D3
Double Command (3 relays) with Single Outputs and
Common Output without feedback
− CF_D3
Double Command (3 relays) with Single Outputs and
Common Output with feedback
− C_D4
Double Command (4 relays) with Double Outputs without
feedback
− CF_D4
Double Command (4 relays) with Double Outputs with
feedback
− C_D2N
Double Command (2 relays) with Single Outputs Negated
without feedback
− CF_D2N
Double Command (2 relays) with Single Outputs Negated
with feedback
• Measured Values:
Configuration
5-13

Advertisement

Table of Contents