Appendix
A-12
A
B
C
Important! Cable shield grounding must be done on the cable side!
Note:
Figure A-8
Current connections to three current transformers and a core balance neutral
current transformer for ground current - preferred for effectively or low-resistance
grounded networks
A
B
C
Important! Cable shield grounding must be done on the cable side!
Note:
Figure A-9
Current connections to two current transformers and core balance neutral current
transformer for sensitive ground fault detection - only for ungrounded or compen-
sated networks
Panel Surface Mounted
Flush-mounted/Cubicle
Ia
15
Q1
Ib
14
Q3
Ic
13
Q5
3I
0
27
Q8
7SJ62
Change of Address 0201 setting changes polarity of 3I
Input !
Panel Surface Mounted
Flush-mounted/Cubicle
Ia
15
Q1
Ib
14
Q3
Ic
13
Q5
I
NS
27
Q8
7SJ62
Change of Address 0201 setting changes polarity of I
Input !
Q2
30
Q4
29
Q6
28
Q7
12
Current
0
Q2
30
Q4
29
Q6
28
Q7
12
Current
NS
7SJ62 Manual
C53000-G1140-C121-1