6.14.2.1 Settings for Automatic Reclosing

Addr.
LCD-Text
7101
FCT 79
7SJ62 Manual
C53000-G1140-C121-1
The auto reclose function can be blocked, if control commands are issued. The control
information must be routed via CFC (interlocking task-level) using the
CMD_Information block (see Figure 6-59).
"IN: Control Device
52 Breaker CF_D12"
Figure 6-59
Blocking of the auto reclose function using the internal control function
Not applicable for version 7SJ61**–**A**– and 7SJ61**–**M**
At address  =21( 6(4&225', the zone sequencing feature can be turned 21
or 2)). If zone sequencing is turned on, then the device counts the number of reclos-
ing attempts made by sequenced devices via flow measurement so that tripping can
be blocked for based on the reclosing attempt of another device.
At addresses  to , reclosing can be initiated or blocked for various types of
protective elements.
At addresses  to , it is possible to block tripping by various types of protec-
tive elements subsequent to any of the first four reclosing attempts. The settings in
these addresses are used when zone sequencing is turned on and if the protection of
load side fuses against temporary fault is desired. Zone sequencing is enabled in ad-
dress .
Setting Options
Default Setting
OFF
OFF
ON
Comments
Automatic reclosing
Functions
"OUT: >BLOCK 79"
Ordering Code
7SJ62**–
X
X
X