Functions
6.13.2.1 Settings for Breaker Failure Protection
Addr.
LCD-Text
7001
FCT 50BF
7004
Chk BRK CONTACT
7005
TRIP–Timer
6.13.2.2 Information List for Breaker Failure Protection
F#
LCD-Text
1451
50BF OFF
1452
50BF BLOCK
1453
50BF ACTIVE
1456
50BF int Pickup
1457
50BF ext Pickup
1471
50BF TRIP
1480
50BF int TRIP
1481
50BF ext TRIP
1403
>BLOCK 50BF
1431
>50BF ext SRC
4601
>52-a
4602
>52-b
6-128
Setting Options
OFF
ON
OFF
ON
~
0.06
60.00 sec
50BF Breaker failure protection switched OFF
50BF Breaker failure protection is BLOCKED
50BF Breaker failure protection is ACTIVE
50BF (internal) PICKUP - after internal BFI
50BF (external) PICKUP - after external BFI
50BF Breaker failure TRIP
50BF Breaker failure (internal) TRIP, int. BFI
50BF Breaker failure (external) TRIP, ext. BFI
>BLOCK 50BF Breaker failure protection
>50BF initiated externally
>52-a contact (OPEN, if breaker is open)
>52-b contact (OPEN, if breaker is closed)
Default Setting
OFF
50BF Breaker failure protection
OFF
Evaluation of breaker auxiliary con-
tacts (52/a or 52/b) via binary inputs
0.25 sec
Timer to indicate failure
Comments
Comments
7SJ62 Manual
C53000-G1140-C121-1