Automatic Reclosing System (79M); Description Of Automatic Reclosing System - Siemens SIPROTEC 7SJ62 Instruction Manual

Multi-functional protective relay with bay controller
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

6.14

Automatic Reclosing System (79M)

6.14.1 Description of Automatic Reclosing System

General
Trip Command
Breaker Status
52-a
Dead Time
Reclose Command
Reset Time
(Blocking Time)
Reclosing
Successful
Figure 6-56
Timing Diagram for a Second Successful Reclosure
7SJ62 Manual
C53000-G1140-C121-1
From experience, the majority of faults associated with overhead distribution feeders
are temporary in nature. Therefore, to maximize service availability, it is desirable to
employ a system that will close the circuit breaker shortly after it is tripped. This is ac-
complished in the 7SJ62 relay via the automatic reclosing system.
When using the automatic reclosing system, if the fault still exists after the circuit
breaker has been reclosed, then the protective elements will re-trip the circuit breaker.
Depending on the number of reclosing attempts programmed for the automatic reclos-
ing system (up to nine are possible), the circuit breaker will either be reclosed again,
or will remain open.
The automatic reclosing function is typically utilized only in situations where the occur-
rence of temporary faults is anticipated. Therefore, the automatic reclosing system is
not applied when the 7SJ62 relay is used to protect generators, motors, transformers,
and cables.
The automatic reclosing function can also be initiated by an external protection relay.
For this application, an output contact from the tripping relay must be wired to a binary
input of the 7SJ62 relay. It is also possible to allow the 7SJ62 relay to work in conjunc-
tion with an external reclosing device.
Figure 6-56 shows an example of a timing diagram for a successful second reclosure.
Figure 6-57 shows an example of a timing diagram for two unsuccessful reclosing
shots, with no additional reclosing of the circuit breaker.