Siemens SIPROTEC 7SJ62 Instruction Manual page 232

Multi-functional protective relay with bay controller
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Functions
Addr.
LCD-Text
4001 FCT 46
4002 46-1 PICKUP
4003 46-1 DELAY
4004 46-2 PICKUP
4005 46-2 DELAY
4006 46 IEC CURVE
4007 46 ANSI CURVE
4008 46-TOC PICKUP
4009 46-TOC TIMEDIAL
4010 46-TOC TIMEDIAL
4011 46-TOC RESET
6-92
= 1 A, divide the Setting Options values and Default Setting values by 5. Consider the
current transformer ratios when setting the device with primary values.
Setting Options
ON
OFF
0.50 ~ 15.00 A
0.00 ~ 60.00 sec
0.50 ~ 15.00 A
0.00 ~ 60.00 sec
Normal Inverse
Very Inverse
Extremely Inverse
Extremely Inverse
Inverse
Moderately Inverse
Very Inverse
0.50 ~ 10.00 A
0.50 ~ 15.00 sec
0.05 ~ 3.20 sec
Instantaneous
Disk Emulation
Default Setting
OFF
Negative sequence current
protection
0.50 A
Pickup current 46-1
1.50 sec
Definite delay time 46-1
2.50 A
Pickup current 46-2
1.50 sec
Definite delay time 46-2
Extremely Inv.
Current-time IEC
characteristic curve 46-
TOC
Extremely Inv.
Current-time ANSI
characteristic curve 46-
TOC
4.50 A
Pickup current 46-TOC
5.00 sec
Time dial, ANSI
characteristics, 46-TOC
0.50 sec
Time multiplier, IEC
characteristics, 46-TOC
Instantaneous
Reset characteristic for 46-
TOC, ANSI current-time
characteristics
Comments
Configu-
ration
X X X
X X X
X X X
X X X
X X X
7SJ62 Manual
C53000-G1140-C121-1
X
X
X
X
X
X
X
X X
X
X
X