Siemens SIPROTEC 7SJ62 Instruction Manual page 224

Multi-functional protective relay with bay controller
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Functions
Addr.
LCD-Text
3106
VPH MIN
3107
VPH MAX
3109
1
)
64-1 VGND
3110
2
)
64-1 VGND
3111
T-DELAY
Pickup.
3112
64-1 DELAY
3113
50Ns-2 PICKUP
3114
50Ns-2 DELAY
3115
67Ns-2 DIRECT.
3117
50Ns-1 PICKUP
3118
50Ns-1 DELAY
3119
51Ns PICKUP
3120
51Ns TIME DIAL
3122
67Ns-1 DIRECT.
3123
RELEASE
DIRECT.
3124
PHI CORREC-
TION
3125
MEAS. METHOD
3126
RESET DELAY
3130
PU CRITERIA
3131
M.of PU TD
6-84
Setting options
Default Setting
10 ~ 100 V
40 V
10 ~ 100 V
75 V
1.8 ~ 130.0 V
40.0 V
10.0 ~ 225.0 V
70.0 V
0.4 ~ 320.00 sec
1.00 sec
0.10 ~ 40000.0 sec 10.00 sec
0.003 ~ 1.500 A
0.300 A
0.00 ~ 320.00 sec
1.00 sec
Forward
Forward
Reverse
Non-Directional
0.003 ~ 1.500 A
0.100 A
0.00 ~ 320.00 sec
2.00 sec
0.003 ~ 1.400 A
0.100 A
0.10 ~ 4.00 sec
1.00 sec
Forward
Forward
Reverse
Non-Directional
0.003..1.200 A
0.010 A
-45.0..45.0 °
0.0 °
COS Phi
COS Phi
SIN phi
0..60 sec
1 sec
Vgnd OR INs
Vgnd OR INs
Vgnd AND INs
1
) if address 0213: Vab, Vbc, VGnd
2
) if address 0213: Van, Vbn, Vcn
Comment
Voltage of faulty phase Vph min
Voltage of
phase
Unfaulted
Vph max
64-1 Ground Displacement Voltage
64-1 Ground Displacement Voltage
Time-DELAY Pickup
64-1 Time Delay
50Ns-2 Pickup
50Ns-2 Time Delay
67Ns-2 Direction
50Ns-1 Pickup
50Ns-1 Time delay
51Ns Pickup
51Ns Time Dial
67Ns-1 Direction
Release directional element
Correction Angle for Dir. Determina-
tion
Measurement method for Direction
Reset Delay
Sensitive Ground Fault PICKUP crite-
ria
Multiples of PU
Time-Dial
Configu-
ration
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
7SJ62 Manual
C53000-G1140-C121-1

Advertisement

Table of Contents
loading