Table 5-5
Selection Guide for Function Modules and Task Levels
Function Modules
ABSVALUE
Magnitude calculation
AND
AND-Gate
BOOL_TO_CO
Boolean to control (conversion)
BOOL_TO_DI
Boolean to Double Point
BUILD_DI
Create Double Point annunciat.
CMD_INF
Test
CONNECT
Connection
D_FF
D-Flipflop
DI_TO_BOOL
Double Point to Boolean
LIVE_ZERO
Live-zero, non linear Curve
LOWER_SETPOINT Lower limit
NAND
NAND-Gate
NEG
Negator
NOR
NOR-Gate
OR
OR-Gate
7SJ62 Manual
C53000-G1140-C121-1
Within the Run Sequence menu, select (GLW, and then 3UHGHFHVVRU IRU ,Q
VWDOODWLRQ, to ensure that the function modules selected from the library will be im-
plemented into the desired task level (Figure 5-32).
Figure 5-32
Assignment of Function Modules to the Selected Task Level
The proper assignment is important for several reasons. For example, if interlocking
logic were to be set up in the measured values (Meter processing) run-time sequence
level, indications would constantly be created by the cyclical processing, filling the
buffer unnecessarily. On the other hand, the interlocking condition at the moment of a
control operation may not be processed at the right time, since meter processing is
done only every 600 ms.
Description
Task Level
MW_BEARB
PLC1_BEARB
Meter processing
Slow PLC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Configuration
PLC_BEARB
SFS_BEARB
Fast PLC
Interlocking
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5-33