Configuration
CLOSING
Command
C+1
C+2
C–1
C–2
Relay Configuration:
Figure 5-8
Double Command with Double Contacts (with 4 Relays)
CLOSING
Command
C+1
C+2
C–
Relay Configuration:
Figure 5-9
Double Command with Double and Single Contacts (with 3 Ralays)
5-10
TRIP
Command
BO 1
2
3 4
X
X
X X
TRIP
Command
BO 1
2 3
X
X
X
Note:
It is recommended to mask Trip and Close commands from a protection function the
same binary I/O's, if they operate the same breaker. If for instance, the Close com-
mand of the Control function uses two contacts the auto reclose function should be
masked also to both contacts. See elementary diagrams in the appendix A.
C+1
C+2
t
C+1
C+2
t
V+
C–1
Switching Device
CLOSE
TRIP
COIL
COIL
C–2
V–
V+
C–
Switching Device
CLOSE
TRIP
COIL
COIL
V–
7SJ62 Manual