SCADA Interface
7SJ62 Manual
C53000-G1140-C121-1
– Laser Class 1 Under EN 60825–1/ –2 using glass fiber 50/125 µm or
– Optical Link Signal Attenuation
– Channel Distance
– Character Idle State
Profibus–FMS or
IEC 60870–5–103
RS232
– Connection for flush mounted case
for panel surface-
mounted case
– Test Voltage
– Transmission Speed
– Maximum Distance of Transmission
RS485
– Connection for Flush Mounted Case
for panel surface-
mounted case
– Test Voltage
– Transmission Speed
– Maximum Distance of Transmission
Profibus RS485
– Connection for Flush Mounted Case
for panel surface-
mounted case
– Test Voltage
Transmission Speed
– Maximum Distance of Transmission
Profibus–FMS
Fibre Optical Link
– Connection
For Flush-Mounted Case
using glass fiber 62.5/125 µm
max. 8 dB, with glass fiber 62.5/125 µm
max. 1.5 km (0.95 miles)
selectable: factory setting "Light off"
floating interface for data transfer
to a master terminal
rear panel, mounting location "B"
9 pin DSUB port
at the terminal on the case bottom
500 V AC
min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
15 meters / 49 feet
rear panel, installation location "B"
9 pin DSUB Port RS 485
at the terminal on the case bottom
Profibus cable
500 V AC
min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
1 km / 3280 feet / 0.62 mile
rear panel, installation location "B"
9 pin DSUB Port RS 485
at the terminal on the case bottom
500 V AC
up to 12 M Baud
1 km / 3280 feet / 0.62 mile at≤ 93.75 kBd
500 m /1640 feet /0.31 mile at≤ 187.5 kBd
200 m / 660 feet at
100 m / 330 feet at
integrated ST connector for OWG
direct access,
single ring or twin ring, depending on order
rear panel, mounting location "B"
Technical Data
≤ 1.5 MBd
≤ 12 MBd
10-5