Configuration
Configuring a
Function Key as a
Source
5-22
Note :
A single logical indication should not be configured to two binary inputs, since an OR-
link of both signals is not ensured. The operating program allows only one link, and
deletes the first link when a second is established. Use CFC to perform an "25" in-
stead.(
In addition, a single point indication cannot be configured to a binary input and to CFC
as a source at the same time. In this case, an error message would be displayed. Click
on 2., and select another configuration.
Error Message Resulting from Double Configuration
Figure 5-23
If a double point indication (DP) is configured to one binary input (e.g., feedback indi-
cations from switching devices), the next binary input is also set. If this configuration
is undone, the second binary input is automatically deconfigured.
If a transformer tap changer indication is configured to a binary input, the next binary
inputs in order are also configured. Their total number is the same as the number of
bits configured for the transformer tap changer. If one of these inputs is deconfigured,
all related binary inputs are automatically deconfigured.
The four function keys on the front of the relay may also be configured as sources in
order to establish a link using CFC. In this situation, each function key may be linked
with only one internal indication. A function key may be occupied because it has al-
ready been set as an operating function for the relay. As delivered from the factory ,
the device's function keys F1, F2, and F3 are preconfigured:
F1
operating messages
F2
primary measured values
F3
overview of the last eight fault messages
Note:
When an indication is configured to a function key, its factory-assigned function is de-
leted. Reestablishment of the factory default function of the F-keys is only possible by
initializing the relay with a new factory parameter set created within DIGSI
vice settings have to be reentered.
In order to configure a new indication, select one of the options (OPEN/CLOSE, ON/
OFF, etc.) from the indication group in the information catalog and drag it to the left
®
4. All de-