Siemens SIPROTEC 7SJ62 Instruction Manual page 480

Multi-functional protective relay with bay controller
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Appendix
Addr.
Setting Title
1513
MANUALCLOSEMODE
1514
67 active
1515
Normal Load
1516
67 Direction
1530
67
1531
MofPU Res T/Tp
1601
FCT 67N/67N-TOC
1602
67N-2 PICKUP
1603
67N-2 DELAY
1604
67N-1 PICKUP
1605
67N-1 DELAY
1607
67N-TOC PICKUP
1608
67N-TOC T-DIAL
1609
67N-TOC T-DIAL
1610
67N-TOC RESET
1611
67N-TOC IEC
1612
67N-TOC ANSI
1613
MANUALCLOSEMODE
1614
67N active
1615
Normal Load
1616
67N Direction
A-20
Setting Options
67-2 instantaneously
67-2 instantane-
67-1 instantaneously
ously
67-TOC instantane-
ously
Inactive
with 79 active
always
always
Inductive (135°)
Inductive (135°)
Resistive (90°)
Capacitive(45°)
Forward
Forward
Reverse
OFF
OFF
ON
0.25..175.00 A
2.50 A
0.00..60.00 sec
0.10 sec
0.25..175.00 A
1.00 A
0.00..60.00 sec
0.50 sec
0.50..20.00 A
1.00 A
0.05..3.20 sec
0.20 sec
0.50..15.00
5.00
Instantaneous
Disk Emulation
Disk Emulation
Normal Inverse
Normal Inverse
Very Inverse
Extremely Inverse
Long Inverse
Very Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Extremely Inverse
Definite Inverse
67N-2 instantaneously
67N-2 instantane-
67N-1 instantaneously
ously
67N-TOC instantane-
ously
Inactive
always
always
with 79 active
Inductive (135°)
Inductive (135°)
Resistive (90°)
Capacitive(45°)
Forward
Forward
Reverse
Default Setting
Manual Close Mode
67 active
Normal Load (Torque angle of dir. fct)
Phase Direction
67
Multiple of Pickup <-> T/Tp
67N, 67N-TOC Ground Time Over-
current
67N-2 Pickup
67N-2 Time Delay
67N-1 Pickup
67N-1 Time Delay
67N-TOC Pickup
67N-TOC Time Dial
67N-TOC Time Dial
Drop-Out Characteristic
IEC Curve
ANSI Curve
Manual Close Mode
67N active
Normal Load (Torque angle of dir. fct)
Ground Direction
Comments
7SJ62 Manual
C53000-G1140-C121-1