Functions
Addr.
LCD-Text
7155
67–TOC/67N–
TOC
7156
sens Ground Flt
7157
46
7158
BINARY INPUT
7159
3Pol.PICKUP BLK YES
7170
1.Cy: 50(N)–1
7171
1.Cy: 50(N)–2
7172
1.Cy: 67(N)–1
7173
1.Cy: 67(N)–2
7174
2.Cy: 50(N)–1
7175
2.Cy: 50(N)–2
7176
2.Cy: 67(N)–1
7177
2.Cy: 67(N)–2
7178
3.Cy: 50(N)–1
7179
3.Cy: 50(N)–2
6-140
Setting Options
Default Setting
No influence
No influence
Starts 79
Stops 79
No influence
No influence
Starts 79
Stops 79
No influence
No influence
Starts 79
Stops 79
No influence
No influence
Starts 79
Stops 79
NO
NO
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Not Blocked
Not Blocked
Blocked Via 79
Comments
67–TOC and 67N–TOC supervi-
sion of automatic reclosing
Sensitive ground fault detection
supervision of automatic reclos-
ing
46–1, 46–2, and 46N–TOC su-
pervision of automatic reclosing
(one setting)
Binary input supervision of auto-
matic reclosing (phase and
ground)
3 pole trips block automatic re-
closing
Automatic reclosing control of
50–1 and 50N–1 during first
shot
Automatic reclosing control of
50–2 and 50N–2 during first
shot
Automatic reclosing control of
67–1 and 67N–1 during first
shot
Automatic reclosing control of
67–2 and 67N–2 during first
shot
Automatic reclosing control of
50–1 and 50N–1 during second
shot
Automatic reclosing control of
50–2 and 50N–2 during second
shot
Automatic reclosing control of
67–1 and 67N–1 during second
shot
Automatic reclosing control of
67–2 and 67N–2 during second
shot
Automatic reclosing control of
50–1 and 50N–1 during third
shot
Automatic reclosing control of
50–2 and 50N–2 during third
shot
Ordering Code