False Echo Mapping - Emerson Rosemount 5708 Reference Manual

3d solids scanner
Hide thumbs Also See for Rosemount 5708:
Table of Contents

Advertisement

Configuration - Rosemount 5708L
November 2017
5.3.3

False Echo Mapping

When the configuration is finished, set False Echo Mapping.
38
<tag name>
3.45m Avg Dist.
█████████████▒▒▒▒▒
Menu
Basic Settings
Advanced Settings
False Echo Mapping
Polling Address
Map False Echoes
Reset Mapping
False Echo Area
Distance To Map
False Echo
00.000 m
Decline Mapping
Approve Mapping
Decline Mapping
Approve Mapping
1. From the main screen, select the
2. In the main menu, scroll down to False Echo Mapping, using the
key.
Select
to switch to the False Echo Mapping configuration
E
screen.
3. Select Map False Echoes for automatically mapping all the false
echoes up to a certain distance.
Or select Reset Mapping for deleting the stored mapped false
echoes from the memory.
Use the
key to go down the list. Select
a. If Map False Echoes is selected, set the distance from the top
of the antenna assembly to the end of the scanning point.
Always make sure to map false echoes above material level.
The recommended level is 3 ft. (1 m) above actual material
level.
Use the
key to switch between the two digits. Use the
key to modify the value. Select
b. Approve or decline the false echo mapping operation.
Use the
key to go down the list. Select
c. If Reset Mapping is selected, approve or decline the
operation. Use the
continue.
Reference Manual
00809-0100-4570, Rev DA
key to enter the main menu.
E
to continue.
E
to continue.
E
to continue.
E
key to go down the list. Select
Configuration - Rosemount 5708L