Operation
November 2017
Figure 7-104. Center of Gravity Settings
7.5.18
Level by Section Output
The option to output the level per section is licensed. Enter the activation code in Tools > Server Options
> License Key. Click to Apply button to accept the code and close the window.
By activating this feature the 3DVision can output the minimal, maximal, and average level in each
section. The level in each section is calculated from the 3D image of the material in the vessel and
displayed in the 3D image.
To set the Sections, right-click the vessel when in site view mode, select Properties... and switch to the
General tab, see
1. Set the number of sections on X axis and the number of sections on Y axis; the total number of
sections is equal to X * Y and limited to 99 sections. Set the number of sections to 1 in order to
deactivate this feature.
2. Minimal size of a section cannot be smaller than 5ft.
3. Right -click the 3D image, select Misc and select Show Sections. This will show the grid of sections on
top of the 3D image. See Figure 109 for an example of six sections.
4. Calculated section levels can also be read via SCADA connection on Modbus registers. The holding
registers are:
41001 – Sec 1 Avg. Level
41003 – Sec 1 Min Level
41005 – Sec 1 Max Level
41021 – Sec 2 Avg. Level
41023 – Sec 2 Min Level
41025 – Sec 2 Max Level
41041 – Sec 3 Avg. Level
41043 – Sec 3 Min Level
41045 – Sec 3 Max Level