Rosemount LinkPro Operating Instructions
November 2017
Selecting connection cable
The Rosemount LinkPro is connected to a power supply with a standard cable that meets local regulatory
standards. RS-485 rated cable with screening should be used to connect the sensors. Screening is
necessary to ensure interference-free operation with other devices. The communication cable should be
twisted pair and shielded, rated for a RS-485 communication standard, and have 120 Ohm impedance.
Cable screening and grounding
The communication cable shield must be grounded. Connect the shield in the Rosemount 5708
grounding point on one end and to a dedicated grounding on the other end. This can be, for example,
the '-' port of the power supply.
D.5.2

Wiring plan

This section provides details of how to connect the wires.
Power supply
Detailed information on the power supply can be found in the
To connect to a power supply:
1. Loosen the four Rosemount LinkPro housing screws using a flat screwdriver.
2. Remove the housing cover.
3. Insert the Rosemount 5708 cable through the left gland of the Rosemount LinkPro.
4. Loosen the terminals with a small, flat screwdriver.
5. Connect the power supply wires to sockets "1" and "2" in accordance with
polarity.
6. Tighten the screws of the terminal.
7. Tighten the compression nut of the cable entry. The seal ring must wrap the cable completely.
8. Connect sockets "3" and "4" with a separate cable to the Rosemount LinkPro.
9. Screw on the Rosemount LinkPro housing cover.
10.If the cable is screened, refer to
173
"Cable screening and grounding" on page
Reference Manual
00809-0100-4570, Rev DA
"Technical specifications" on page
Figure
D-6. Note the
173.
Rosemount LinkPro Operating Instructions