Always observe the following safety instructions:
Connections must be made only in the complete absence of line voltage.
If over-voltage is expected, overvoltage arresters should be installed.
Use only a safety-certified power supply with dual insulation between the primary and output for
powering the unit. The power supply output rating must be limited to 18-32 Vdc, 1 A for a single
Rosemount 5708, and not to be connected to a DC distribution network.
The 4-20mA lines should NOT be connected in multi-drop.
Using the Rosemount 3DVision to communicate with the units allow the user to choose one of several
communication types: RS-485, GSM, GPRS or TCP/IP, for more information and details regarding the
communications, refer to the
Wire the Rosemount 5708
1. Verify the power supply is disconnected.
2. Loosen the compression nut of the cable gland entry.
3. Insert the cable through the cable gland entry.
Electrical Installation
"Communication methods" on page
Electrical Installation