Reference Manual
00809-0100-4570, Rev DA
Figure 7-60. Advanced Parameters - Beams Activation
7.5.3
Device current simulation settings
The output current can be simulated by setting Volume (%), or Current (mA). This feature is useful for
synchronizing with the PLC and verifying of identical read values for both the Rosemount 5708 and the
PLC.
1. On the Device menu, select Device Current Simulation Settings or press F6.
2. Select Volume or Current Simulation from the drop down list and fill the value field, volume can be
between 0 to 100%. Current simulation settings can be between 4 to 20mA.
3. Select Apply to set the changes in the device, to stop current simulation select 'Simulation Off' and
select Apply.
The Current simulation status of the device may be terminated by either restart or power reset.
Figure 7-61. Current Simulation Settings
Note
Turn off current simulation by selecting Simulation Off and select Apply.
Operation
Operation
November 2017
101