Emerson Rosemount 5708 3D Solids Scanner DeltaV Series Manual Supplement
Emerson Rosemount 5708 3D Solids Scanner DeltaV Series Manual Supplement

Emerson Rosemount 5708 3D Solids Scanner DeltaV Series Manual Supplement

Integration

Advertisement

Quick Links

Manual Supplement
00809-0300-4570, Rev BA
Rosemount
Integration with DeltaV
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Network setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Using direct connection to DeltaV with a serial card . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
Configuring byte order for connection via serial card . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Workaround procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
Configuring serial card in DeltaV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
Configuring control strategies to obtain correct process values . . . . . . . . . . . . . . . . . . page 23
Setting up 3DVison in DeltaV operate screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 27
1.0

Introduction

This document indicates how to setup and configure Rosemount 5708 3D Solids Scanner with DeltaV
using two different methods. Configuration details are included for the physical network, DeltaV
Explorer, 3DMultiVision
necessary component for one of the setups which DeltaV communicates with the 3DMultiVision server
through. DeltaV Explorer configuration is performed on the DeltaV ProPlus Station; 3DMultiVision and
VIMNet configuration is performed on an application station.
1. The scanner is directly connected to DeltaV Serial Card. Using the 3DMultiVision software to view
3D images 3D image from the scanner is not possible in direct connection.
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
5708 Series 3D Solids Scanner
Client, and VIMNet. The VIMNet application interfaces with the VIM card - a
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
1

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 5708 3D Solids Scanner DeltaV Series

  • Page 1: Table Of Contents

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 ™ Rosemount 5708 Series 3D Solids Scanner ™ Integration with DeltaV Introduction ............. .page 1 Specifications .
  • Page 2: Specifications

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 2. The scanner is connected to the Application station via RS485/USB or RS485/TCP converter. The 3DMultiVision software is installed on the Application station. The DeltaV VIM can read the scanner data from the 3DMultiVision server on the Application station.
  • Page 3: Network Setup

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Network setup To be able to run 5708 3DMultiVision software simultaneously with DeltaV, set up the network as follows: 1. Setup a network switch connected to the DeltaV controller, the DeltaV ProPlus station, and the DeltaV Application Station.
  • Page 4 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Configuring 3DMultiVision software 1. Launch the 3DVision Client application on the Application Server. 2. If necessary, create a new project and setup the device. Under Connection Type, select TCP/IP or select the COM port in which the RS485 to USB converter is connected to.
  • Page 5 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 6. In a multi-scanner system, where a vessel in the 3DVision is configured with multiple scanners it is possible to view the vessel's data on the SCADA, use the vessel ID to set the connection between the DeltaV to the 3DVision.
  • Page 6 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 5. The IP Address of the VIM can be set to any available IP on the network; the availability of an IP can be checked using the Ping function at the bottom left of the pop up window. Select OK when all of the parameters are set correctly.
  • Page 7 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 10. Set the Device Address to the 3D Solids Scanner's SCADA ID. This first serial port (P01) can be configured to communicate with the 5708 3DMultiVision server. Select Add to add the IP definition of the device.
  • Page 8 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 15. Upload the new configuration. Right-click the desired VIM and select Upload Configuration to VIM. Confirm the upload to the VIM by selecting Yes in the window that will appear, and save the changes.
  • Page 9 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 5. In the Card type list, select 2 Ports, Programmable RS232|RS485. 6. In the Slot position list, select 57. Figure 1-4. Add a 2 Port Programmable RS232|RS485 Serial Card on Slots 57-60 7.
  • Page 10 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 10. On the Port tab, select the Enabled check box. 11. On the Advanced tab, use the following settings: Mode: master  Retry count: 10 ...
  • Page 11 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 13. Select OK. 14. Right-click on the port which was just enabled and select New Serial device. This device will represent the 3D Solids Scanner device. The Properties window opens. 15.
  • Page 12 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 b. On the DeltaV tab, in the DeltaV data type list, select the appropriate data type for the values which are to be retrieved. Table 1-1. Registers Number Register number Parameter...
  • Page 13 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 On the PLC tab, use the following settings: Device data type 3  Data start address: enter the start address. For example, if the first value should be 'Avg ...
  • Page 14: Using Direct Connection To Deltav With A Serial Card

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 19. If a multidrop connection is desired, each scanner should be linked with a device instance under the associated virtual serial port. Additionally, the required Datasets should be created. Repeat steps14 through to add each device;...
  • Page 15: Configuring Byte Order For Connection Via Serial Card

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Configuring byte order for connection via serial card ® Modbus is an application layer messaging protocol, positioned at level 7 of the OSI model, which provides client/server communication between devices connected on different types of buses or networks.
  • Page 16: Workaround Procedure

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Workaround procedure 1. To get the correct values to decode each 16-bit word to individual bits, the words will be swapped to match with the transmission sequence used by the Rosemount 5708 3D Solids Scanner. 2.
  • Page 17 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 4. In the Card class list, select Serial Cards. 5. In the Card type list, select 2-Ports, RS232/RS485. In the Card series list, select Series 2 for M series hardware. For S series there is no choice. 6.
  • Page 18 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 8. On the Port tab, select the Enabled check box. 9. On the Advanced tab, use the following settings: Protocol type: RTU  Mode: Master ...
  • Page 19 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 10. On the Communications tab, use the following settings: Port type: RS422/RS485 half duplex  Baud rate: 115200  Parity: even  Data bits: 8 ...
  • Page 20 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 15. Expand the port with the newly added device. 16. Right-click on the new device and select New Dataset. Note Repeat step to add more Datasets. When a multidrop connection is used, add the desired datasets under each device instance.
  • Page 21 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 b. On the DeltaV tab, in the DeltaV data type list, select the appropriate data type for the values which are to be retrieved. See figures on Example setup for dataset constructed to read the first 12 parameters Example setup for dataset constructed to read the “Tag Name”...
  • Page 22 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Table 1-4. Configuration for Two Datasets that Display a 3D Solids Scanner’s 13 Parameters Parameter Dataset 1 Dataset 2 DeltaV data type 16 bit unit w/Status String w/Status PLC data type Holding registers...
  • Page 23: Configuring Control Strategies To Obtain Correct Process Values

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Configuring control strategies to obtain correct process values 1. The parameter “Tag Name” is read correctly by DeltaV. No additional configuration is required with regard to the value; it can be used directly from its Dataset. 2.
  • Page 24 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Figure 1-7. Function Block Properties and Variables in the Control Strategy for Floating Points AI1. Set up the Dataset in the filed Device PV. Parameter type should be Floating MANTISSA.
  • Page 25 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Figure 1-8. Expression in CALC Block Control Strategy for Floating Points 4. For the parameter SN (Serial Number), the byte order must be swapped and converted from binary to long integer.
  • Page 26 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 5. In the control strategy, set up the following parameters in the function blocks and variables: a. AI1: For Device Tag, use Browse… to add the newly defined Dataset (Dataset1). For Parameter, assign the first Modbus register (40023).
  • Page 27: Setting Up 3Dvison In Deltav Operate Screen

    Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Setting up 3DVison in DeltaV operate screen Assumption Modbus communications have been established between DeltaV and Rosemount 5708  3DMultiVision Server Modbus register 49990 in the 5708 3DVision server software is being read via Modbus. Check if .enc ...
  • Page 28 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Configure button 1. Double click the button and type a label. 2. Select and drag on arrows around button to resize. 3. Right click to launch context menu. 4.
  • Page 29 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Edit script ® ® 1. Select Edit Script to open the Microsoft Visual Basic program. Place the cursor in the correct position to edit the script which runs when the button is pushed. The need for a script is to launch the viewer from a remote server so it is not resident on the DeltaV Pro Plus station.
  • Page 30 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 2. Command line breakdown: Command Line Definition \\usrtc-smartlab1 Name of server Shared drive that contains 3DVision Server software program files \program files Path to software (x86)\3DVisionEmrsn\binclient\bin\ visualvision3dviewer .exe Image display program.
  • Page 31 Manual Supplement Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV 00809-0300-4570, Rev BA 2016 Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV...
  • Page 32 Conditions of Sale page. +971 4 8118100 The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. +971 4 8865465 All other marks are the property of their respective owners.

Table of Contents