Fire alarm setting is used to configure other alarm inputs as the fire alarm input. Fire alarm input does
not follow the arm delay time, it has the highest priority. It is triggered as long as the alarm input defined
as fire alarm is configured. All 10 alarm inputs can be defined fire alarm input.
5.9.5.4
Alarm Action Setting
Alarm Action Setting is used to configure the allocation between the physical alarm input and the output
on main module, door module and alarm module.
Press
to configure alarm action setting when the following window appears.
NAV Controller provides total 18 alarm outputs: 2 alarm outputs on main module, 8 alarm outputs on
door module, 8 alarm outputs on alarm module. They are allocated in 3 submenus, shown as the below
windows:
The first menu is "Alarm Act Setting on Main Module". Press
shows the current status of the alarm output. Y indicates the alarm output is enabled; N indicates the
alarm output is disabled.
The main module provides two alarm outputs, press key "1" and "2" to toggle the alarm output 1, 2 ON
and OFF
Press
to switch to "Alarm Act Setting on Door Module" submenu. Press
LCD screen shows the current status of the alarm relay outputs on the door module.
Up to 4 door modules can be installed on the NAV Controller. 2 alarm outputs are available on each door
module. As a result, up to 8 alarm outputs can be available if 4 door modules are installed. Press numeric
key 1~8 to toggle the alarm output on door module between ON and OFF.
Press
to switch to "Alarm Act Setting on Extern Module" submenu. Press
setting, LCD screen shows the current status of the alarm outputs on alarm module.
One alarm module can be installed on the NAV Controller. 8 alarm outputs are available on alarm
module. Press numeric key 1~8 to toggle the alarm output on alarm module between ON and OFF.
Note the "Alarm Output on Alarm Module" is only shown when alarm module is installed on the
controller.
Fire Alarm
Fire alarm input
Alarm Action Setting
Alarm Act Setting
on Main Moudle
Alarm Act Setting
on Door Moudle
Alarm Act Setting
on Extern Moudle
Alarm act on main
YN
Alarm act on door
NNNNNNNN
Alarm act on alarm
NNNNNNNN
Fire Alarm
Other alarm input
to enter to the setting, LCD screen
50
NAV IP Access Controller
to enter to the setting,
to enter to the