4 FUNCTIONS

4.2.2 Communication with the remote device stations

Personal computer
Program
mdReceive
mdReceive
4 - 5
This section explains an overview of the communication between the master station
and the remote device station.
In the communication with the remote device station, the handshaking signals with the
remote device station (initial data processing request flag, error reset request flag, etc.)
are communicated using the remote input RX and remote output RY. Numeric data
(averaging processing specification, digital output values, etc.) is communicated using
the remote register RWw and remote register RWr.
3)
Read
4)
mdSend
Write
6)
mdSend
Write
9)
Read
Master station
CC-Link Ver.2 board
1)
Network
parameters
Buffer memory
Remote input RX
Link scan
Remote output RY
Link scan
Remote register
Link scan
RWw
Remote register
Link scan
RWr
MELSEC
Remote device station
Remote input
RX
2)
Handshaking signals
such as remote READY
and initial data
processing request flag
Remote input
RY
5)
Handshaking signals
such as error reset
request flag and initial
data processing
complete flag
Remote register
RWw
7)
Numeric data such
as for averaging
processing setting
and A-D conversion
enable/disable setting
Remote register
8)
RWr
Numeric data such
as digital output
values and detected
temperature value
4 - 5