4 FUNCTIONS
4 - 17
[Data link startup]
1) When the personal computer is powered on, the CC-Link system automatically
starts up in accordance with the network parameters set by the CC-Link Ver.2
utility.
[Remote input]
2) The remote input RX of the intelligent device station is automatically stored (for
each link scan) in the "remote input RX" buffer memory of the master station.
3) The program uses the mdReceive function to read the input status stored in
the "remote input RX" buffer memory.
Personal computer
Program
mdReceive
[Remote input RX when the AJ65BT-D75P2-S3 is
Signal direction: AJ65BT-D75P2-S3
Device No.
RX00
RX01
RX02
RX03
RX04
RX05
RX06
RX07
RX08
to
Master station
CC-Link Ver.2 board
Remote input RX
RX0F to RX00
RX1F to RX10
RX2F to RX20
RX3F to RX30
3)
RX4F to RX40
RX5F to RX50
RX6F to RX60
RX7F to RX70
RX8F to RX80
to
RX7FF to RX7F0
set to station number 1]
Signal name
D75P2 ready complete
Single-axis start complete
Dual-axes start complete
Use prohibited
Single-axis BUSY
Dual-axis BUSY
Use prohibited
Single-axis positioning complete
Dual-axis positioning complete
MELSEC
Intelligent device station
(Station number 1:
occupies 4 stations)
Remote input RX
Handshaking signals
such as positioning
complete
RX0F to RX00
RX1F to RX10
RX2F to RX20
RX3F to RX30
2)
RX4F to RX40
RX5F to RX50
RX6F to RX60
RX7F to RX70
Master module
to
4 - 17