Mitsubishi Electric Q81BD-J61BT11 User Manual page 80

Network interface board melsec cc-link system master/local interface board
Table of Contents

Advertisement

4 FUNCTIONS
Master station
Remote
Remote
input RX
output RY
RX00 to RX0F
RY00 to RY0F
RX10 to RX1F
RY10 to RY1F
RX20 to RX2F
RY20 to RY2F
RX30 to RX3F
RY30 to RY3F
RX40 to RX4F
RY40 to RY4F
RX50 to RX5F
RY50 to RY5F
Master station
Remote
Remote
input RX
output RY
RX00 to RX0F
RY00 to RY0F
RX10 to RX1F
RY10 to RY1F
RX20 to RX2F
RY20 to RY2F
RX30 to RX3F
RY30 to RY3F
RX40 to RX4F
RY40 to RY4F
RX50 to RX5F
RY50 to RY5F
4 - 26
(1) Overview of link data transmission when the standby master
function is used
The following provides an overview of link data transmission when the standby
master function is used.
(a) "Master station output" while the master station is controlling the data link
Standby master station
Station number 1
Number of occupied stations: 1
Remote
Remote
input RX
output RY
RX00 to RX0F
RY00 to RY0F
RX10 to RX1F
RY10 to RY1F
RX20 to RX2F
RY20 to RY2F
RX30 to RX3F
RY30 to RY3F
RX40 to RX4F
RY40 to RY4F
RX50 to RX5F
RY50 to RY5F
The master station data sent to the remote input RX in the standby master
station (shown by the shaded areas in the figure above) is used as the
output information when the master station becomes faulty; thus, it should be
transferred to another device using a sequence program.
In addition, when the master station becomes faulty, the transferred data is
transferred to the remote output RY of the standby master station using a
sequence program.
(b) "Master station input" while the master station is controlling the data link
Standby master station
Station number 1
Number of occupied stations: 1
Remote
Remote
input RX
output RY
RX00 to RX0F
RY00 to RY0F
RX10 to RX1F
RY10 to RY1F
RX20 to RX2F
RY20 to RY2F
RX30 to RX3F
RY30 to RY3F
RX40 to RX4F
RY40 to RY4F
RX50 to RX5F
RY50 to RY5F
The remote I/O station data sent to the remote output RY of the standby
master station is being used by the standby master station as the input
information when the standby station operates as a local station; thus, it
does not need to be transferred to another device.
Remote I/O station
Station number 2
Number of occupied stations: 1
X00 to X0F
Y00 to Y0F
X10 to RX1F
Y10 to RY1F
Remote I/O station
Station number 2
Number of occupied stations: 1
X00 to X0F
Y00 to Y0F
X10 to X1F
Y10 to Y1F
MELSEC
Remote I/O station
Station number 3
Number of occupied stations: 1
X00 to X0F
Y00 to Y0F
X10 to X1F
Y10 to Y1F
Remote I/O station
Station number 3
Number of occupied stations: 1
X00 to X0F
Y00 to Y0F
X10 to X1F
Y10 to Y1F
4 - 26