4 FUNCTIONS
Receive station
Send station
Additional mode
Master station
Local station
Additional mode
Intelligent device station
4 - 53
The following table indicates whether send/receive of transient data is
enabled or not.
Master station
Ver.2
Additional
mode
Ver.2 mode
Ver.1 mode
Ver.2 mode
Ver.1 mode
Ver.2 mode
Ver.1 mode
: Transient transmission enabled,
(4) Mismatch between parameter settings and points for the stations
actually mounted
If the extended cyclic parameter setting on the master station is not consistent
with the link points for each station that is actually connected, an error code is
stored into SW0069 of the Q80BD-J61T11N at the master station. Also,
consistency status of each station is stored into SW009C.
When an error code is stored into SW0069, reexamine the parameter settings.
POINT
For details of link special
(5) Precautions for modes between the master and local/standby
master stations
At any of the following settings, an error (error code: B3A0) will occur at the local
station/standby master station.
The mode set at the master station differs from the mode set at the standby
master station.
When the master station is in the remote net ver.1 mode, the local station
setting is the remote net ver.2 mode or remote net additional mode.
When the master station is in the remote net ver.2 mode, the local station is in
the remote net additional mode.
If an error has occurred, correct the mode parameter of the master station/local
station/standby master station.
Ver.1
Ver.2
mode
mode
mode
: Transient transmission disabled, —: Prohibited
register,
refer to Appendix 2.2.
Intelligent device
Local station
Additional
Ver.1
Ver.2
mode
mode
mode
MELSEC
station
Ver.1
mode
4 - 53