APPENDIX
Number
Name
Remote device
station
SW005F
initialization
(65F
)
procedure
H
registration
instruction result
SW0060
Mode setting
(660
)
status
H
SW0061
Host station
(661
)
number
H
SW0062
Module operating
(662
)
status
H
SW0064
No. of retries
(664
)
information
H
SW0065
No. of automatic
(665
)
return stations
H
SW0066
Delay timer
(666
)
information
H
SW0067
Parameter
(667
)
information
H
SW0068
Host parameter
(668
)
status
H
3: Can be used for the master station only.
App - 24
Stores the execution result of the initialization procedure registration
instruction with SB000B.
0
: Normal
Other than 0: Stores the error code (refer to Chapter 15).
Stores the mode setting status.
0: Online (with automatic return)
2: Offline
3: Line test 1
4: Line test 2
6: Hardware test
Stores the station number of the host that is currently in operation.
0
: Master station
1 to 64 : Local station
Stores the operation setting status of the CC-Link Ver.2 board.
b15
b 12 b 11 b 10 b 9
b8 b7 b6 b5 b4 b3 b2 b1 b0
0
to
0
0
0
0
Indicates the retry count setting information when there is an error
response.
1 to 7 (times)
Indicates the setting information for the number of automatic return
stations during one link scan.
1 to 10 (stations)
Indicates the setting information for the scan interval delay time.
0 to 100 (50  s)
Stores the parameter information area to be used.
0
: CPU built-in parameters
H
3
: Dedicated instruction (parameter setting with the RLPASET
H
instruction and data link startup.)
D
: Default parameters (automatically starts CC-Link)
H
Stores the parameter setting status.
0
: Normal
Other than 0: Stores the error code (refer to Chapter 15).
Description
0
Station type
0: Master station/local station
1: Standby master station
(Valid only when b1 is 0)
Master station duplex function
0: Master station duplex function invalid
1: Master station duplex function valid
Input status from the data
link faulty station
0: Clear
1: Hold
Number of occupied stations
00: Occupies 1 station
10: Occupies 2 stations
11: Occupies 3 stations
01: Occupies 4 stations
Slave station refresh/forced clear
setting in case of programmable
controller CPU STOP
0: Refresh
1: Clears compulsorily
Expanded cyclic setting
00: single
01: double
10: quadruple
11: octuple
MELSEC
Availability
( : Available,
: Not available)
Online
Offline
Master
Local
station
station
3
App - 24