8 OPERATING THE UTILITY SOFTWARE
Item
5) Error status
6) Board type
7) Product information
8) IRQ No.
9) ROM version
10) Memory
11) I/O port
12) Present Error
13) Link scan time (ms)
14) Link refresh time (ms)
15) LED information
16) OK button
17) Save SB/SW button
8 - 6
Displays the status of the error currently detected.
Display
Normal
Transport error
Parameter error
CRC error
Timeout error
Abort error
Setting error
Illegal
Displays the model name of the CC-Link Ver.2 board.
Displays the product information (serial No., function version).
Displays the IRQ No.
Displays the ROM version.
Displays the 2-port memory.
Displays the I/O ports.
An error code of the error currently identified on the CC-Link Ver.2 board is indicated in
hexadecimal notation.
When no error is currently detected, "No Error" is displayed.
Displays the maximum, minimum and current link scan times.
Displays the maximum, current and minimum link refresh time of the CC-Link Ver.2 board.
"Block data assurance per Station" indicates "0" when disabled.
Displays the following LED states.
LED
Color
RUN
Green Operating normally.
ERR.
Red
All stations are faulty.
Due to cable
disconnection or noise
TIME
Red
affecting the transmission
path, no responses are
received from all stations.
Operating as the master
MST
Green
station
SW
Red
Switch setting error
LINE
Red
Cable disconnection error
Operating as a standby
S MST
Green
master station
M/S
Red
Station duplicated error
Operating as a local
LOCAL
Green
station
PRM
Red
Parameter error
Closes the Board detail information screen.
Saves the information of all the CC-Link Ver.2 board SB/SW areas selected on this screen in
CSV format.
Description
Description
Normal status
An error was detected in the transmission path.
A parameter error was detected.
An error in the received data was detected.
A timeout error was detected in data reception.
An error was detected in data communications.
An error was detected in the station No./station type setting, the
transmission rate setting or the mode setting.
An error arising from some other cause was detected.
ON
OFF
A WDT error has
occurred, or the board
is being reset.
No communication error
has occurred, or the
board is being reset.
Responses received
from all stations
Operating as other than
the master station
No switch setting error
No cable disconnection
error
Operating as other than
the standby master
station
Station not duplicated
Operating as other than
the local station
No parameter error
MELSEC
Flashing
There is a faulty
station or station No.
is duplicated.
8 - 6