4 FUNCTIONS
4.4.7 Increasing the number of cyclic points (Remote net ver.2 mode, Remote net additional
mode)
Occupies 1 station
Occupies 2 stations
Occupies 3 stations
Occupies 4 stations
4 - 45
This function increases the number of cyclic points in the CC-Link system.
When increasing the number of cyclic points, select one from the following two modes.
Remote net ver.2 mode ................... Mode used for configuring a new system
Remote net additional mode............ Mode used for incorporating an additional Ver.2
The number of cyclic points per station can be increased as indicated in the following
table.
Remote I/O (RX, RY)
Remote register (RWw, RWr)
Remote I/O (RX, RY)
Remote register (RWw, RWr)
Remote I/O (RX, RY)
Remote register (RWw, RWr)
Remote I/O (RX, RY)
Remote register (RWw, RWr)
REMARK
In the remote net ver.1 mode, the number of cyclic points cannot be increased.
compatible slave station into the existing Ver.1
system
Table 4.7
Expanded cyclic setting
single
double
32 points
32 points
4 points
8 points
64 points
96 points
8 points
16 points
96 points
160 points
12 points
24 points
128 points
224 points
16 points
32 points
MELSEC
quadruple
octuple
64 points
128 points
16 points
32 points
192 points
384 points
32 points
64 points
320 points
640 points
48 points
96 points
448 points
896 points
64 points
128 points