5 PROCEDURE BEFORE STARTING THE DATA LINK
5.4 Wiring
Power OFF the personal computer.
Wire the network cables to the terminal block.
If the terminal block has been removed for wiring, install the
terminal block.
Power ON the personal computer.
5.4.1 Preparation before wiring
5 - 7
This section explains the cable wiring and precautions.
The following shows the wiring procedure.
Start
↓
Power OFF
↓
Wire the cables
↓
Install the terminal block
↓
Power ON
↓
End
Before wiring, check the cables and terminating resistors to be used.
(1) Cables that can be used
The following cables can be used:
• Ver.1.10-compatible CC-Link dedicated cable
• CC-Link dedicated cable (Ver.1.00-compatible)
• CC-Link dedicated high-performance cable (Ver.1.00-compatible)
These cables cannot be used together. If used, normal data transmission is not
guaranteed.
(2) The order of connecting the cables
The cables do not have to be connected in the order of station number.
(3) Terminating resistors to be used
Connect the terminating resistors included with the stations at both ends of the
stations in the CC-Link system.
The terminating resistors to be used vary depending on the cable.
Ver.1.10-compatible CC-Link dedicated cable
CC-Link dedicated cable (Ver.1.00-compatible)
CC-Link dedicated high-performance cable
(Ver.1.00-compatible)
• • • Section 5.4.2 (1) Mounting and removing
Cable type
MELSEC
a terminal block
Terminating resistor to be used
110Ω 1/2W (Brown-Brown-Brown)
130Ω 1/2W (Brown-Orange-Brown)
5 - 7