Mitsubishi Electric Q81BD-J61BT11 User Manual page 126

Network interface board melsec cc-link system master/local interface board
Table of Contents

Advertisement

6 PARAMETER SETTINGS
Setting item
1) Sta. No./Type
2) Transmission rate
3) Mode
Operational settings
4) Expanded cyclic
5) Occupied Sta.
6
6) Input for Err. Sta.
Other settings
7) Retry count
8) Automatic
reconnection
station count
9) Standby master
station No.
10) Delay
information
setting
11) Driver WDT
Monitoring Time
12) Block data
assurance per
station
13) Link refresh
cycle
1: When the driver WDT function is enabled, the recommended value 250 will be displayed in the set value of driver WDT
monitoring time irrespective of the previous set value.
2: The link refresh cycle can be set only when block data assurance per station setting is enabled.
3: When the block data assurance per station is enabled, the recommended value 1 will be displayed in the set value of
link refresh cycle irrespective of the previous set value.
6 - 2
Table 6.1 Parameter setting items list
Description
Sets a station No. and a type of the own station.
Setting range
Sta. No.: 0, 1 to 64 (Default: 1)
Type:
When Sta. No. is 0:Master station,
When Sta. No. is 1 to 64: Local station
(Default), Standby master station
Set the transmission speed of the CC-Link Ver.2 board.
Setting item:
156kbps, 625kbps, 2.5Mbps, 5Mbps,
10Mbps (Default)
Set the operation mode of the own station.
Setting item:
Remote net ver.2 mode
Remote net additional mode
Remote net ver.1 mode (Default)
Offline
Make the expanded cyclic setting when increasing the
number of cyclic points. (Can be set in remote net ver.2
mode or remote net additional mode)
Setting item:
single (Default), double, quadruple,
octuple
Set the occupied station count by the own station.
Setting item:
occupies 1 station (Default), occupies
2 stations, occupies 3 stations,
occupies 4 stations
Set how to handle the input data in the event of a data
link error.
Setting item:
Hold, Clear (Default)
Set the number of retries to be performed when a
communication error occurs.
Setting range: 1 to 7 (Default: 3)
Set the number of slave stations that can be returned to
the network within 1 link scan.
Setting range: 1 to 10 (Default: 1)
Set the station number of the standby master station.
Setting range: 0 to 64 (Default: 0)
Set 0 to "Delay information setting".
Set the driver WDT monitoring time. (Unit: 8ms)
Select "Use driver WDT function" to enable this function.
Setting range: 1 to 32767 (Default: No setting)
Set the block data assurance per station to enable/disable.
Select "Assure block data" to enable this function.
(Default: Disable)
2
Set the link refresh cycle.
(Unit: ms)
Setting range: 1 to 1000 (Default: No setting)
: Setting not required
: Setting required
Local station
Master
Standby
station
master station
1
3
MELSEC
Reference
section
Section
4.3.4
----
----
Section
4.4.7
----
----
----
Section
4.3.2
Section
4.3.4
----
----
Section
4.3.6
----
6 - 2