Configuration Of The Profisafe Addresses (Drives) - Siemens SINUMERIK 840D sl Configuration Manual

Sinumerik step 7 toolbox v14 sp1
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Safety configuration
9.7 Configuring Safety Integrated (SPL)
9.7.7

Configuration of the PROFIsafe addresses (drives)

The PROFIsafe addresses (F-source address, F-destination address) are used to uniquely
identify the source and the destination.
Note
Problem solution for the 27220, 27221 alarms (Safety Integrated (SPL))
• Alarm27220: "PROFIsafe: Number of NCK-F modules (6) <> number of S7-F modules
(0)"
• Alarm27221: "PROFIsafe: NCK-F module MD$MN_PROFISAFE_IN_ADDRESS[0]
unknown or"PROFIsafe: NCK-F module MD $MN_PROFISAFE_OUT_ADDRESS[0]
unknown"
Even if you reuse the existing machine data settings (e.g. using an existing SINUMERIK
archive), you can change the PROFIsafe addresses. In this case, alarms 27220 and 27221
are displayed in SINUMERIK Operate.
You must also modify or augment the details in MD10385, as described here.
Rules for configuring F-source addresses
When Safety Integrated (SPL) is used, you must enter the associated F-source addresses in
the MD10385[0..2]. A maximum of three different F-source addresses are permitted
throughout the system.
You can view the assigned F-source addresses in the PLC properties under "Fail-safe > F-
source addresses".
The assignment method of the F-source address in the TIA Portal depends on the used
device type:
● Drive device based on the device description file:
The configured F-source address can be set in the properties of the telegram under
"PROFIsafe > F_Source_Add".
Requirement
● The software options for Safety Integrated (SPL) are licensed and enabled in the
associated machine data.
● A maximum of three different F-source addresses are used in the configuration.
You can view the used F-source addresses in the PLC properties under "Fail-safe > F-
parameters". If more than three different F-source addresses are used, you must
standardize the F-source addresses because a maximum of three different F-source
addresses can be entered in the MD1385.
● The current configuration is compiled and loaded into the PLC.
● The MD10385, MD10386, MD10387, MD10388 and MD10389 machine data items are
not yet filled.
188
SINUMERIK STEP 7 Toolbox V14 SP1
Configuration Manual, 05/2017, A5E41846325