Safety configuration
9.7 Configuring Safety Integrated (SPL)
9.7.3

Parameterizing F-input modules

The F-modules and F-submodules to be configured must be selected individually in order to
make the desired settings in the "Properties" inspector window. You can select the modules
and submodules in the device view or device overview (in the case of GSD-based devices,
only in the device overview).
You can set the I/O addresses in the properties of the F-modules and F-submodules. These
I/O addresses must lie within the process image of the PLC. (default setting: 1024 bytes; can
be configured under "Cycle" in the PLC properties).
You can select F-modules and F-submodules in the device view or device overview of the
rack.
Procedure
To configure the inserted F-input modules, select them successively and make the settings
individually for each module in the inspector window. Proceed as follows:
1. In the device view, select the rack and open the device overview.
2. In the device overview, select on the rack one of the modules to be configured.
3. In the "Properties > General" inspector window, select the "I/O addresses" entry.
4. Select the "OB1-PA" in the "Process image" dropdown list in each of the "Input
addresses" and "Output addresses" sections.
5. Enter the desired address in the associated "Start address" text field. Note the following:
– The I/O addresses must lie within the process image of the PLC (default setting: 1024
– Do not use any I/O addresses that are used for some other purpose, e.g. by the
180
bytes; can be configured under "Cycle" in the PLC properties).
machine control panel.
SINUMERIK STEP 7 Toolbox V14 SP1
Configuration Manual, 05/2017, A5E41846325