Configuring the NCU
2.5 Loading and closing the hardware configuration in the PLC
2.5
Loading and closing the hardware configuration in the PLC
Requirement
Note
General reset before loading into a PLC with Safety Integrated plus (F-PLC)
If the actual hardware has been operated in Safety Integrated plus (F-PLC) mode and you
now want to load a configured hardware configuration with changed Safety Integrated mode,
you must perform a general reset of the PLC prior to the loading.
Procedure
Proceed as follows to load the configured hardware configuration into the PLC:
1. In the project tree, right-click "CNC_1" and select the "Hardware (changes only)"
command in the "Compile" shortcut menu.
The consistency of the hardware configuration is tested in the compilation process.
Correct any errors that may occur before proceeding.
Note
Compilation
In the compilation process, all integrated subcomponents of the NCU (PLC, NCK, CP,
HMI, SINAMICS Integrated) are also compiled. In addition, all optional components
connected to the NCU (e.g. NX, ADI4) are also compiled.
30
SINUMERIK STEP 7 Toolbox V14 SP1
Configuration Manual, 05/2017, A5E41846325