The TP instruction outputs TRUE while the set time elapses after the timer starts.
Instruction
TP
Timer Pulse
Variables
Name
Meaning
In
Timer input
PT
Set time
Q
Timer
output
ET
Elapsed
time
* T#0ms to T#106751d_23h_47m_16s_854.775807ms
Bit strings
In
OK
PT
Q
OK
ET
Function
The TP instruction outputs TRUE while the set time elapses after the timer starts. The time is set in
nanoseconds. The timer starts when timer input In changes to TRUE and timer output Q changes to
TRUE. Elapsed time ET is incremented as time elapses. When ET reaches set time PT, timer output Q
changes to FALSE. ET is not incremented after that. The timer is reset when In changes to FALSE. ET
changes to 0. The timer is not reset even if In changes to FALSE after the timer starts but before ET
reaches PT.

NY-series Instructions Reference Manual (W560)

Name
FB/FUN
FB
I/O
Description
TRUE: Timer start signal
FALSE: Timer reset signal
Input
Time that Q remains at
TRUE
TRUE: Timer output ON
FALSE: Timer output OFF
Output
Elapsed time since timer
started
Graphic expression
TP_instance
TP
In
Q
PT
ET
Valid range
Depends on data type.
*
Depends on data type.
*
Integers
2 Instruction Descriptions
ST expression
TP_instance (In, PT, Q,
ET);
Unit
Default
---
FALSE
ms
0
---
---
ms
Times, durations,
dates, and text strings
OK
OK
2
2-135