2 Instruction Descriptions
A
0
B
T#10ms
EN
InitVal
UINT#0
UINT#10
EndVal
StepVal
UINT#1
EN
INT#0
In
NEXT
EN
C
0
Precautions for Correct Use
• These instructions must be used in a ladder diagram. They cannot be used in ST. They also cannot
be used in inline ST in a ladder diagram.
• Always connect In directly to the left bus bar. You cannot pass a variable or constant to In.
• Always use the MC and MCR instructions as a pair in the same POU.
• Always place the MCR instruction after the MC instruction.
• Do not nest the MC and MCR instructions to more than 15 levels.
• If there is inline ST in the master control region, the inline ST is not executed when the master control
region is reset.
2-76
MC
In
ENO
MCNo
TON_instance
TON
In
Q
def
PT
ET
FOR
ENO
position
Index
MOVE
ENO
array[position]
Out
ENO
D
FALSE is output.
E
MCR
EN
ENO
MCNo
Reset.
abc
These are not executed.
NY-series Instructions Reference Manual (W560)