It is converted into a large data type to operate the binary operations with a different data type. Therefore,
USHORT does not become valid. The target binary operations are shown below.
• Addition (+)
• Subtraction (-)
• Multiplication (*)
• Division (/)
• Remainder (%)
• Bit logical AND (&)
• Bit logical OR (|)
• Bit exclusive logical OR (^)
(Example)
W0: F=#0F+USHORT(DOL)
USHORT does not become valid.
64-bit floating point type