6-6. Remaining Battery Level Setting
This setting can be used to set the remaining battery level to be reserved for the event of a prolonged power outage.
No discharging is performed when the remaining battery is lower than the
the operation mode (i.e. gird or stand-alone).
• During remote-control system mode, discharging is stopped at the level of remaining battery level adding 2 for
blackout.
Since normal operations will no longer be operable when the set value is lower than the set remaining battery if
the remaining battery is set via the remaining battery level setting, be careful in setting this.
The work must be performed
Preparation
■
See 6-2 to 6-4 and switch to the parameter item selection mode showing the initial display [no1-1]. Then select [no1-2]
and press "MENU(ENTER)" to switch "Remaining Battery Level [Prb **]".
Operation Procedure
■
Parameter Item
Selection (See 6-4)
* Only while [no 1-2] is
being displayed
Display Example
(1)
(2)
(1) Indicates that this is a
remaining battery level
setting.
(2) Displays the current
setting value.
by qualified personnel.
Display Mode
Remaining Battery Level
(Initial Display)
value specified in this setting, regardless of
Setting Mode
Remaining Battery
Level Setting
or
or
65