Locations Where the Storage Battery System Cannot be Installed
x Locations where it will receive or be subject to the impact of continuous direct sunlight.
x Locations that exceed the operating temperature range.
x Locations where the sunlight hits directly in the north or west side of the buildings without roof (eaves).
* See "■ Guidelines how to protect the product from direct sunlight" in the installation manual.
x Rooms such as solariums and greenhouses.
x Locations on moving objects such as trailer houses or cruisers.
x Locations where
strong reflected sunlight strikes during the day.
x Enclosed locations
with insufficient heat radiation. (Storage Battery Systems require free air to keep cool. Installation in confined/
enclosed spaces such as garden sheds or in close proximity to other appliances (i.e. air conditioner) that have the potential of
impeding free air flow is not permitted.)
x Locations where the product may potentially become buried in snow. (Install a roof or a fence if installing the product in
snowbound regions.)
x Locations where humidity, salinity, sulfur or nitrate concentration are constantly high.
x Locations where the required installation space is not available.
* See "■ Clearance space for the
x Locations exposed to or which potentially could be exposed to excessive steam, oil vapour, smoke, dust, corrosive substances,
explosive/flammable gases, chemicals, fire or exhaust gas from vehicles.
x Locations subject to extreme temperature fluctuations. (Where dew condensation occurs.)
x Locations with strict noise requirements. (Operational noise of 40dB or lower.)
x Locations subject to impacts, shocks or vibrations caused by such as vehicle passing, machine operating, dropping, kicking or
acting of vandalism.
x Locations in the proximity of equipment/devices that are susceptible to radio interference, or locations that are emitting powerful
radio waves.
x Locations unable to bear the weight of the product.
x Locations where concrete foundations or equivalent floor materials cannot be laid.
x Regions where there is severe salt pollution.
x Locations where above sea level is below 0 m.
x On the upper floors or the roof of the building.
50 mm
Lithium-ion Storage Battery System
200 mm
200 mm
Clearance space for Lithium-ion Storage Battery System
" below explanation.
50 mm
800 mm